Heat resistant rubber insulated non sheathed, cables for internal wiring of electrical & electronic appliances in dry area

Cable Structure

Conductor:

Fine Stranded Flexible Copper to VDE 0295 IEC 60228

Insulation:

Rubber compound EI3, Halogen free, DIN VDE -282

Colour:

Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Grenn, Yellow or other colours

Flame propagation:

Flame retardant test as per IEC 60332-1

Cable features

  • Special heat resistant rubber insulation
  • High current carrying capacity
  • High elasticity
  • Excellent resistant to moisture, abrasion, grace, oil
  • Longer flex life
  • Excellent mechanical & electrical properties
  • Harmonized acc. to European standards
  • Tested by SGS, EIL, RITES, NPC, INTERTEK
  • Download
  • this PDF file for Complete information
    on Single core flexible cables

Technical DataTable

HO5G-K (300/500 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C
Lower limit Upper limit
sqmm mm mm mm Ω / km
0.5 0.6 2.0 2.4 39.0
0.75 0.6 2.1 2.6 26.0
1 0.6 2.3 2.7 19.5
  • All are class 5 flexible conductor
  • Insulation grade is EI3
HO7G-K (450/750 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C
Lower limit Upper limit
sqmm mm mm mm Ω / km
1.5 0.7 3 3.7 13.3
2.5 0.8 3.6 4.5 7.98
4 0.8 4.3 5.4 4.95
6 0.8 4.8 6 3.30
10 1.0 6 7.6 1.91
16 1.0 7.1 8.9 1.21
25 1.2 8.8 11 0.780
35 1.2 10.1 12.6 0.554
50 1.4 11.9 14.9 0.386
70 1.4 13.6 17 0.272
95 1.6 15.2 19.3 0.206
120 1.6 17.1 21.4 0.161
150 1.8 19 23.8 0.129
185 2.0 21 26.3 0.106
240 2.2 23.9 29.4 0.0801
  • All are class 5 flexible conductor
  • Insulation grade is EI3