quit

Cable Structure

generally conforms to IS 1554-1, IEC 60502-1, BS 6346

Conductor Material - Copper According to VDE 0295 class 1 or 2 (IEC 60228,IS 8130)
Insulation PVC Type A as per IS:5831
Inner Sheath PVC
Outer Sheath PVC TYPE ST-1 OF IS : 5831

TECHNICAL DATA

Operating Temp. -20°c to max.+90°C
Nominal voltage 1100 V
Test voltage 3000 V
Insulation resistance Min. 10 MΩ x km
Min. bending radius Single core :15 X Overall diameter
   Multi core :12 X Overall diameter
Flame propagation Flame retardant test as per IEC 60332-1

Application

PVC Unarmoured Cables
Power cables for energy supply are installed outdoors, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected.

Standard length cable packing:
Coils 100, 200, 300, 500, 1000 m. in wooden reels

Color Coding: AS IS 1554 ( Indian Standard )

Single core 2 Core 3 Core 4 Core 5 Core
Red or Black Red, Black Red, Yellow, Blue Red, Yellow, Blue, Black Red, Yellow, Blue, Black, Grey

Color coding: AS IEC 60502 Part-1, B.S. 6346

Single core 2 Core 3 Core 4 Core 5 Core
Black or Yellow/Green Blue and Brown or Yellow-Green and Black Brown, Black, Grey or Yellow/Green, Blue, Brown Blue, Brown, Black, Grey or Yellow/Green, Brown, Black, Grey Blue, Brown, Black, Grey, Black or Yellow/Green, Blue, Brown, Black, Grey

Technical DataTable

JAINSON 1.1 Kv 3 CORE COPPER CONDUCTOR XLPE INSULATED , INNER SHEATHED UN.ARMOURED PVC SHEATHED CABLES (IS : 7098 PART 1 )
CABLE CODE : 2X-Y
SIZE (MM2) INSULATION XLPE THICKNESS IN MM (NOM.) INNER SHEATH PVC THICKNESS IN MM (MIN.) OUTER SHEATH PVC THICKNESS IN MM (MIN.) APPROX OUTER SHEATH O/D IN MM APPROX WEIGHT OF CABLE (KGS./KM) MAX.DC CONDUCTOR RESISTANCE
at 20° C (Ohm/Km)
Current Ratings (Amp.)
Direct In Ground In Air
3 C X 1.50.700.301.8011.6018512.102322
3 C X 2.50.700.301.8012.352267.413030
3 C X 40.700.301.8013.853044.614439
3 C X 60.700.301.8014.953793.085550
3 C X 100.700.301.8017.105411.837467
3 C X 160.700.302.0020.058001.159485
3 C X 250.900.402.0020.109460.727120125
3 C X 350.900.402.0021.9512410.524145155
3 C X 501.000.402.0024.8517000.387170190
3 C X 701.100.502.0027.9522550.268210235
3 C X 951.100.502.2031.4530340.193250290
3 C X 1201.200.502.2034.5538010.153285330
3 C X 1501.400.602.2038.3047020.124315375
3 C X 1851.600.602.4042.2557370.0991355435
3 C X 2401.700.702.6047.0572710.0754410510
3 C X 3001.800.702.8051.7090110.0601460590
3 C X 4002.000.703.0058.75119530.0470520670

Technical DataTable

JAINSON 1.1 Kv 3.5 CORE COPPER CONDUCTOR XLPE INSULATED , INNER SHEATHED UN.ARMOURED PVC SHEATHED CABLES (IS : 7098 PART 1 )
CABLE CODE : 2X-Y
SIZE (MM2) INSULATION XLPE THICKNESS IN MM (NOM.) INNER SHEATH PVC THICKNESS IN MM (MIN.) OUTER SHEATH PVC THICKNESS IN MM (MIN.) APPROX OUTER SHEATH O/D IN MM APPROX WEIGHT OF CABLE (KGS./KM) MAX.DC CONDUCTOR RESISTANCE
at 20° C (Ohm/Km)
Current Ratings (Amp.)
MAIN CORE HALF CORE Direct In Ground In Air
3½ X 250.900.700.302.0022.4011220.727120125
3½ X 350.900.700.302.0024.2014160.524145155
3½ X 501.000.900.302.0027.9019740.387170190
3½ X 701.100.900.402.2031.9526600.268210235
3½ X 951.101.000.402.2035.9035690.193250290
3½ X 1201.201.100.502.4040.4045560.153285330
3½ X 1501.401.100.502.4043.6554650.124315375
3½ X 1851.601.100.602.6048.7567910.0991355435
3½ X 2401.701.200.702.8054.3085990.0754410510
3½ X 3001.801.400.803.0060.05106490.0601460590
3½ X 4002.001.600.803.4068.20140040.0470520670
3½ X 5002.201.701.003.6076.10175370.0366580750