Flexible Rubber Submersible pump cables

Cable Structure

generally conforms to, CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, IEC 245, CEI 20-19 & BS 6007, BS 6899

Copper:

EC flexible copper generally conforms to IEC 60228, DIN VDE 0295,IS 8131

Insulation:

Special Rubber EPR, EPDM core

Outer Sheath

Special Rubber : Black, Blue

*Any other Color on specific request can also be supplied

Cable features

  • Meets the requirement of CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, UL-83 IEC 245, CEI 20-19 & BS 6007, BS 6899
  • Temperature range -40° to +90°
  • Designed for heavy duty use
  • Cur, tear & abrasion resistant
  • Exceptional long term performance
  • Excellent resistant to oils, chemicals, ozone & solvents
  • Excellent Impact Resistant
  • Excellent Weather Resistant
  • Performs & Looks like Vulcanize Rubber
  • Excellent Electrical Properties
  • Approved by GWSSB, GWRDC, TWAD, PHED, PSTC, ONGC
  • Tested by INTERTEK,SGS, EIL, RITES, NPC

Cable Design

Jainson H07RN-F cables are a specialized product to be used for submersible pumps in a deep well. The area of installation is physically restrictive, and the environment is very hostile. Jainson is designed and manufactured keeping in mind these factors to achieve the highest possible degree of reliability.

Cores colour: Core Identification
Color coding As per IEC 60227 As per IS 694
3 Core Black, Light Blue and Brown Red, Yellow and Blue
4 Core Black, Light Blue, Brown, Yellow with Green Line/ Green with Yellow Line Red , Yellow, Blue, Green / Black
  • Download
  • this PDF file for Complete information
    on Single core flexible cables

Technical DataTable

H07RN-F - 3 core
Number of cores & cross sectional area of conductor Nominal insulation thickness Nominal thickness of sheath Mean overall dimeter Max conductor resistance at 20°C
Lower lmit Outer limit
nxsqmm mm mm mm mm Ω / km
1.5 0.8 1.6 9.2 11.9 13.3
2.5 0.9 1.8 10.9 14 7.98
4 1 1.9 12.7 16.2 4.95
6 1 2.1 14.1 18 3.30
10 1.2 3.3 19.1 24.2 1.91
16 1.2 3.5 21.8 27.6 1.21
25 1.4 3.8 26.1 33 0.780
35 1.4 4.1 29.3 37.1 0.554
50 1.6 4.5 34.1 42.9 0.386
70 1.6 4.8 38.4 48.3 0.272
95 1.8 5.3 43.3 54 0.206
H07RN-F - 4 core
Number of cores & cross sectional area of conductor Nominal insulation thickness Nominal thickness of sheath Mean overall dimeter Max conductor resistance at 20°C
Lower lmit Outer limit
nxsqmm mm mm mm mm Ω / km
1.5 0.8 1.7 10.2 13.1 13.3
2.5 0.9 1.9 12.1 15.5 7.98
4 1 2 14 17.9 4.95
6 1 2.3 15.7 20 3.30
10 1.2 3.4 20.9 26.5 1.91
16 1.2 3.6 23.8 30.1 1.21
25 1.4 4.1 28.9 36.6 0.780
35 1.4 4.4 32.5 41.1 0.554
50 1.6 4.8 37.7 47.5 0.386
70 1.6 5.2 42.7 54 0.272
95 1.8 5.9 48.4 61 0.206
  • The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360