HO7RN-F 450/750 V
Heavy-duty H07RN-F harmonized cable built with robust rubber insulation and flexible copper conductors for demanding industrial and outdoor applications. Its excellent resistance to oil, water, abrasion and weathering makes it ideal for portable power supplies, construction sites, pumps, generators and mobile equipment. Designed under European harmonized standards for superior flexibility and durability.
Cable Structure
Generally Conforms to, DIN VDE 0282 PART 810, IEC 245, BS7655,BS7919/ HD22.1, HD22.4
Conductor : Flexible Class 5 copper conductor according to DIN VDE 0295,IEC 60228
Insulation :
EPDM-rubber, core identification by colours
Sheathing :
Weather - and oil resistant rubber Black or Blue,
*Any other Color on specific request can also be supplied
Technical Data
Operating Temp :
-25°c to max.+90°C
Nominal Voltage :
450/750 V
Test Voltage
: 2500 V
Min. bending radius
: 8 x cable diameter
Flame propagation :
Flame retardant test as per IEC 60332-1
Applications
HO7RN-F
- JAINSON H07RN-F rubber insulated and sheathed cables are intended for flexible connection to electrical equipment. They are suitable for both indoor and outdoor use in industrial and agricultural plant and on construction sites.
- JAINSON H07RN-F rubber insulated and sheathed cables are intended for flexible connection to electrical equipment. They are suitable for both indoor and outdoor use in industrial and agricultural plant and on construction sites.
Standard length cable
packing:
- Coils 100 and 200 m in carton boxes, reels
- Coils 100 and 200 m in carton boxes, reels
Cable Features
Temperature range -30° to +90°
Designed for heavy duty use
Cur, tear & abrasion resistant
Exceptional long term performance
Excellent resistant to oils, chemicals, ozone & solvents
Excellent Weather Resistant
Performs & Looks like Vulcanize Rubber
Excellent Electrical Properties
Approved by GWSSB, GWRDC, TWAD, PHED, PSTC, ONGC
Tested by INTERTEK,SGS, EIL, RITES, NPC
One Core
| Sq. mm | Nos/ dia. (Nom.) | Insulation
Thicknes in mm ( nom.) |
Core dia. In mm | Sheath Thickness in mm (nom.) |
Cable dia. In mm (Nom.) |
Max. C.R in ohm/km Copper |
| 1 C X 1.5 | 22/0.300 | 0.80 | 3.25 | 1.40 | 6.20 | 12.10 |
| 1 C X 2.5 | 36/0.300 | 0.80 | 3.80 | 1.40 | 6.70 | 7.41 |
| 1 C X 4 | 56/0.300 | 0.90 | 4.50 | 1.50 | 7.50 | 4.95 |
| 1 C X 6 | 84/0.300 | 1.00 | 5.25 | 1.60 | 8.60 | 3.30 |
| 1 C X 10 | 140/0.300 | 1.00 | 7.00 | 1.80 | 10.80 | 1.91 |
| 1 C X 16 | 224/0.300 | 1.20 | 8.15 | 1.90 | 12.20 | 1.21 |
| 1 C X 25 | 350/0.300 | 1.20 | 9.95 | 2.00 | 14.20 | 0.780 |
| 1 C X 35 | 490/0.300 | 1.40 | 11.10 | 2.20 | 15.70 | 0.554 |
| 1 C X 50 | 703/0.300 | 1.40 | 13.30 | 2.40 | 18.30 | 0.386 |
| 1 C X 70 | 988/0.300 | 1.60 | 15.15 | 2.60 | 20.60 | 0.272 |
| 1 C X 95 | 1349/0.300 | 1.60 | 17.55 | 2.80 | 23.40 | 0.206 |
| 1 C X 120 | 608/0.500 | 1.80 | 19.45 | 3.00 | 25.70 | 0.161 |
| 1 C X 150 | 760/0.500 | 2.00 | 21.30 | 3.20 | 27.90 | 0.129 |
| 1 C X 185 | 943/0.500 | 2.20 | 23.90 | 3.40 | 30.80 | 0.106 |
| 1 C X 240 | 1225/0.500 | 2.40 | 27.10 | 3.50 | 34.10 | 0.0801 |
| 1 C X 300 | 1498/0.500 | 2.60 | 29.60 | 3.60 | 36.80 | 0.0641 |
| 1 C X 400 | 2035/0.500 | 2.80 | 33.80 | 3.80 | 41.60 | 0.0486 |
Note
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83
Two Core
| Sq. mm | Nos/ dia. (Nom.) | Insulation
Thicknes in mm ( nom.) |
Core dia. In mm | Sheath Thickness in mm (nom.) |
Cable dia. In mm (Nom.) |
Max. C.R in ohm/km Copper |
| 2 C X 1 | 14/0.300 | 0.80 | 3.00 | 1.30 | 8.70 | 18.10 |
| 2 C X 1.5 | 22/0.300 | 0.80 | 3.25 | 1.50 | 9.60 | 12.10 |
| 2 C X 2.5 | 36/0.300 | 0.90 | 3.80 | 1.70 | 11.10 | 7.41 |
| 2 C X 4 | 56/0.300 | 1.00 | 4.50 | 1.80 | 12.90 | 4.95 |
| 2 C X 6 | 84/0.300 | 1.00 | 5.25 | 2.00 | 14.70 | 3.30 |
| 2 C X 10 | 140/0.300 | 1.20 | 6.50 | 3.10 | 19.40 | 1.91 |
| 2 C X 16 | 224/0.300 | 1.20 | 8.00 | 3.30 | 22.70 | 1.21 |
| 2 C X 25 | 350/0.300 | 1.40 | 10.10 | 3.60 | 27.50 | 0.780 |
Note
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83
Three Core
| Sq. mm | Nos/ dia. (Nom.) | Insulation
Thicknes in mm ( nom.) |
Core dia. In mm | Sheath Thickness in mm (nom.) |
Cable dia. In mm (Nom.) |
Max. C.R in ohm/km Copper |
| 3 C X 1 | 14/0.300 | 0.80 | 3 | 1.4 | 9.45 | 18.1 |
| 3 C X 1.5 | 22/0.300 | 0.80 | 3.25 | 1.6 | 10.20 | 12.10 |
| 3 C X 2.5 | 36/0.300 | 0.90 | 3.80 | 1.8 | 11.90 | 7.41 |
| 3 C X 4 | 56/0.300 | 1.00 | 4.50 | 1.90 | 13.50 | 4.95 |
| 3 C X 6 | 84/0.300 | 1.00 | 5.25 | 2.10 | 15.60 | 3.30 |
| 3 C X 10 | 140/0.300 | 1.20 | 6.50 | 3.30 | 20.60 | 1.91 |
| 3 C X 16 | 224/0.300 | 1.20 | 8.00 | 3.50 | 24.20 | 1.21 |
| 3 C X 25 | 350/0.300 | 1.40 | 10.10 | 3.80 | 29.10 | 0.780 |
| 3 C X 35 | 490/0.300 | 1.40 | 11.30 | 4.10 | 32.10 | 0.554 |
| 3 C X 50 | 703/0.300 | 1.60 | 13.30 | 4.50 | 38.10 | 0.386 |
| 3 C X 70 | 988/0.300 | 1.60 | 15.30 | 4.80 | 42.30 | 0.272 |
| 3 C X 95 | 1349/0.300 | 1.80 | 18.00 | 5.30 | 49.10 | 0.206 |
| 3 C X 120 | 608/0.500 | 2.00 | 19.80 | 5.90 | 54.60 | 0.161 |
| 3 C X 150 | 760/0.500 | 2.20 | 22.00 | 6.00 | 59.50 | 0.129 |
| 3 C X 185 | 943/0.500 | 2.400 | 23.70 | 6.50 | 64.30 | 0.106 |
Note
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83
Four Core
| Sq. mm | Nos/ dia. (Nom.) | Insulation
Thicknes in mm ( nom.) |
Core dia. In mm | Sheath Thickness in mm (nom.) |
Cable dia. In mm (Nom.) |
Max. C.R in ohm/km Copper |
| 4 C X 1 | 14/0.300 | 0.80 | 3.00 | 1.5 | 10.7 | 18.10 |
| 4 C X 1.5 | 22/0.300 | 0.80 | 3.25 | 1.70 | 11.2 | 12.10 |
| 4 C X 2.5 | 36/0.300 | 0.90 | 3.80 | 1.90 | 13.00 | 7.41 |
| 4 C X 4 | 56/0.300 | 1.00 | 4.50 | 2.00 | 14.9 | 4.95 |
| 4 C X 6 | 84/0.300 | 1.00 | 5.25 | 2.30 | 17.5 | 3.30 |
| 4 C X 10 | 140/0.300 | 1.20 | 6.50 | 3.40 | 22.6 | 1.91 |
| 4 C X 16 | 224/0.300 | 1.20 | 8.00 | 3.60 | 27.1 | 1.21 |
| 4 C X 25 | 350/0.300 | 1.40 | 10.10 | 4.10 | 32.7 | 0.780 |
| 4 C X 35 | 490/0.300 | 1.40 | 11.30 | 4.40 | 36.2 | 0.554 |
| 4 C X 50 | 703/0.300 | 1.60 | 13.30 | 4.80 | 42.3 | 0.386 |
| 4 C X 70 | 988/0.300 | 1.60 | 15.30 | 5.20 | 48.2 | 0.272 |
| 4 C X 95 | 1349/0.300 | 1.80 | 18.00 | 5.90 | 55.6 | 0.206 |
| 4 C X 120 | 608/0.500 | 2.00 | 19.80 | 6.00 | 61.2 | 0.161 |
| 4 C X 150 | 760/0.500 | 2.20 | 22.00 | 6.50 | 66.00 | 0.129 |
| 4C X 185 | 943/0.500 | 2.40 | 23.70 | 6.90 | 71.5 | 0.106 |
Note
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83
Four Core
| Sq. mm | Nos/ dia. (Nom.) | Insulation
Thicknes in mm ( nom.) |
Core dia. In mm | Sheath Thickness in mm (nom.) |
Cable dia. In mm (Nom.) |
Max. C.R in ohm/km Copper |
| 5 C X 1 | 14/0.300 | 0.80 | 3.00 | 1.60 | 11.50 | 18.10 |
| 5 C X 1.5 | 22/0.300 | 0.80 | 3.25 | 1.80 | 12.60 | 12.10 |
| 5 C X 2.5 | 36/0.300 | 0.90 | 3.80 | 2.00 | 14.50 | 7.41 |
| 5 C X 4 | 56/0.300 | 1.00 | 4.50 | 2.20 | 16.80 | 4.95 |
| 5 C X 6 | 84/0.300 | 1.00 | 5.25 | 2.50 | 19.40 | 3.30 |
| 5 C X 10 | 140/0.300 | 1.20 | 6.50 | 3.60 | 25.10 | 1.91 |
| 5 C X 16 | 224/0.300 | 1.20 | 8.00 | 3.90 | 29.70 | 1.21 |
| 5 C X 25 | 350/0.300 | 1.40 | 10.10 | 4.40 | 36.40 | 0.780 |
| 5 C X 35 | 490/0.300 | 1.40 | 11.30 | 4.60 | 40.00 | 0.554 |
Note