CONSTRUCTION
Structure : Generally conforms to IS 694, BS 6004, IEC 60227, DIN VDE 0281 -3, IS 8130 & IS 5831
Conductor : EC grade flexible copper class 5 generally conforms IEC 60228, IS 8130
Insulation : FR+HR/FRLS-H/ZHFR Insulation compound with a high insulation resistance value (-15°C to +70°C / +90°C/ +105°C)
Core Colours : Red, Blue, Black, Brown, Grey, Orange, White,
Green, Yellow (Any other Colour on specific request can also be supplied)
Application : Fixed installation in conduits and under plaster for Power distribution to electrical appliances & Lighting in Houses, Commercial Complexes, Shopping Malls, Buildings, Industries, Hospitals, Apartments etc.

Standard length cable packing

Coils 90m & 200m in carton boxes, reels

Features of "JAINSON" Flexible Cables (FR/ FRLS/ ZHFR)

For continuous use in deep well to supply power to submersible
motors for the depth upto 500 mtrs.

" FRLF "PVC Insulated cable :
High flame retardant properties
Excellent resistant to moisture, abrasion, grace, oil
Longer Flex Life
Excellent mechanical & electrical properties
Tested by SGS, EIL, RITES, NPC, INTERTEK
Steam and boiling water resistant
"FRLS" PVC Insulated cable :
Better Flame retardant property
Less Halogen acid gas evolution
Resistant to tarnishing of copper
Excellent resistant to moisture, abrasion, grace, oil
Excellent mechanical & electrical properties
"ZHFR" Cable :
Zero Halogen acid gas evolution
Non corrosive and non toxic insulation
High temperature resistant insulation
Resistance to tarnishing of copper

Single Core Industrial Flexible Cable up to 1100V

Nominal cross section area of conductor Number / Nominal dia of strands Nominal Insulation Thickness Approx Overall Diameter Max. Conductor Resistance at 20°C Current Rating
Casing Concealed
Sq. mm mm mm mm ohm/km AMPS AMPS
1.00 14/0.30* 0.70 2.80 18.1 14 13
1.50 22/0.30* 0.70 3.00 12.1 18 16
2.50 36/0.30* 0.80 3.70 7.41 24 20
4.00 56/0.30** 0.80 4.20 4.95 32 26
6.00 84/0.30** 0.80 4.80 3.30 42 35

* Class 2 Stranded conductor
** Class 5 Flexible conductor

FRLS/ ZHFR Properties

Test Specified Specified Values
Limited Oxygen Index Test IS 10810-58 > 29%
Limited Temperature Index Test IS 10810-65 > 250%

FRLS/ ZHFR Properties

Test Specified Specified Values
Limited Oxygen Index Test ASTM-D 2863 > 32%
Limited Temperature Index Test ASTM-D 2863 > 250%
Smoke Density (Light Absorption) ASTM-D 2843 < 50%
Acid Gas Generation 1 EC-607 54-1 < 18%

Note

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360

In view of continuous improvements in our design and process, specifications given here in are subject change without notice.