H05V2-K 300/500 V H07V2-K 450/750 V
Premium H05V2-K harmonized cable with flexible copper core and heat-resistant PVC insulation, engineered for fixed installations in electrical conduits and wiring systems. Offers high current carrying capacity, excellent durability, and stable performance across varying temperatures. Designed to meet stringent European harmonized standards for internal wiring.
Cable Structure
Conductor :
Fine Stranded Copper (Class 5 - Flexible Plain Copper) to VDE 0295 IEC
60228
Insulation : Heat -
resistant PVC core insulation
Color :
Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White,
Green, Yellow or other colours
Flame propagation :
Flame retardant test as per IEC 60332-1
Technical Data
Operating Temp :
-30°C to +90°C
Nominal Voltage :
HO5V2-K : 300/500 V
HO7V2-K : 450/750 V
HO7V2-K : 450/750 V
Test Voltage
: HO5V2-K : 2000 V
HO7V2-K : 2500 V
HO7V2-K : 2500 V
Insulation
resistance : 20 MΩ x km
Min. bending radius
: 4 x cable diameter
Applications
HO5V2-K,
HO7V2-K
- For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
- For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
Standard length cable
packing:
- Coils 100 and 200 m in Carton Boxes, Reels
- Coils 100 and 200 m in Carton Boxes, Reels
Cable Features
Special heat resistant insulation
High Current Carrying Capacitys
Less heat energy radiation
High flexibility
Excellent resistant to moisture, abrasion, grace, oil
Excellent mechanical & electrical properties
harmonized acc. to European standards
Insulation is highly thermal stable
Tested by SGS, EIL, RITES, NPC, INTERTEK
H05V2-K (300/500 V)
| Size in mm |
Nos/ dia. (Nom.) |
Insulation Thickness in mm ( nom.) |
Outer Dia in mm (Appx.) |
Max. C.R in ohm/km Copper |
|---|---|---|---|---|
| 0.5 | 16/0.200 | 0.60 | 2.10 | 39.00 |
| 0.75 | 24/0.200 | 0.60 | 2.20 | 26.00 |
| 1 | 32/0.200 | 0.60 | 2.70 | 19.50 |
All are class 5 flexibility conductor
Insulation grade is TI1
Note
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83
H07V2-K (450/750 V)
| Size in mm |
Nos/ dia. (Nom.) |
Insulation Thickness in mm ( nom.) |
Outer Dia in mm (Appx.) |
Max. C.R in ohm/km Copper |
|---|---|---|---|---|
| 1.5 | 30/0.250 | 0.70 | 3.25 | 13.30 |
| 2.5 | 50/0.250 | 0.80 | 3.80 | 7.98 |
| 4 | 56/0.300 | 0.80 | 4.50 | 4.95 |
| 6 | 84/0.300 | 0.80 | 5.25 | 3.30 |
| 10 | 140/0.300 | 1.00 | 6.50 | 1.91 |
| 16 | 224/0.300 | 1.00 | 8.00 | 1.21 |
| 25 | 350/0.300 | 1.20 | 10.10 | 0.780 |
| 35 | 490/0.300 | 1.20 | 11.30 | 0.554 |
| 50 | 703/0.300 | 1.40 | 13.50 | 0.386 |
| 70 | 988/0.300 | 1.40 | 15.30 | 0.272 |
| 95 | 1349/0.300 | 1.60 | 18.00 | 0.206 |
| 120 | 608/0.500 | 1.60 | 19.80 | 0.161 |
| 150 | 760/0.500 | 1.80 | 22.30 | 0.129 |
| 185 | 943/0.500 | 2.00 | 23.90 | 0.106 |
| 240 | 1225/0.500 | 2.20 | 26.80 | 0.0801 |
All are class 5 flexibility conductor
Insulation grade is TI1