Cable Structure
Conductor : Solid copper conductor, class 1 DIN VDE 0281,IEC 60228
Insulation : Heat - resistant polyvinyl chloride (PVC) insulation
Color : Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours
Flame propagation : Flame retardant test as Per IEC 60332-1
Technical Data
Operating Temp : -20°C to max.+80°C
Nominal Voltage : HO5V2-U : 300/500 V | HO7V2-U : 450/750 V
Test Voltage : HO5V2-U : 2000V | HO7V2-U : 2500V
Insulation resistance : Min. 10 MΩ x km
Min. bending radius : 4 x Cable Diameter
Applications
 HO5V2-U, HO7V2-U
-   For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster
 Standard length cable packing:
-   Coils 100 and 200 m in Carton Boxes, Reels
Cable Features
Special heat resistant insulation
High Current Carrying Capacitys
Less heat energy radiation
Good application of insulation
Excellent resistant to moisture, abrasion, grace, oil
Excellent mechanical & electrical properties
harmonized acc. to European standards
Insulation is highly thermal stable
Tested by SGS, EIL, RITES, NPC, INTERTEK

HO5V2-U (300/500 V)

Size in
mm
Nos/ dia.
(Nom.)
Insulation Thickness
in mm ( nom.)
Outer Dia
in mm (Appx.)
Max. C.R in
ohm/km Copper
0.5 1/0.80 0.60 2.10 36.00
0.75 1/0.97 0.60 2.20 24.50
1 1/1.13 0.60 2.60 18.10
  All are class 2 stranded conductor
  Insulation grade is TI1

Note

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360

HO7V2-U (450/750 V)

Size in
mm²
Nos/ dia.
(Nom.)
Insulation Thickness
in mm ( nom.)
Outer Dia
in mm (Appx.)
Max. C.R in
ohm/km Copper
1.5 1/1.38 0.70 3.00 12.10
2.5 1/1.78 0.80 3.60 7.41
4 1/2.24 0.80 4.10 4.61
6 1/2.24 0.80 4.70 3.08
10 1/3.57 1.00 5.80 1.83
  All are class 2 stranded conductor
  Insulation grade is TI1