x
Cable Structure

generally conforms to IS 1554-1, IEC 60502-1, BS 6346

Conductor : Material - Copper According to VDE 0295 class 1 or 2 (IEC 60228,IS 8130)
Insulation : PVC Type A of IS:5831
Inner Sheath : PVC
Armouring : Single layer of GS round wire or Flat Strips
Outer Sheath : PVC TYPE ST-1 OF IS : 5831
Technical Data
Operating Temp : -20°c to max.+90°C
Nominal Voltage : 1100 V
Test Voltage : 3000 V
Insulation resistance : Min. 10 MΩ x km
Min. bending radius : Single Core : 15X Overall diameter
Multi Core : 12X Overall diameter
Flame propagation : Flame retardant test as per IEC 60332-1
Application
 PVC Armoured Cables
-   Power cables for energy supply are installed outdoors, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are no
 Standard length cable packing
-   Coils 100, 200, 300, 500, 1000 m. in wooden reels

Color Coding: AS IS 1554 ( Indian Standard )

Single Core 2 Core 3 Core 4 Core 5 Core
Red or Black Red, Black Red, Yellow, Blue Red, Yellow, Blue, Black Red, Yellow, Blue, Black, Grey

Color coding: AS IEC 60502 Part-1, B.S. 6346

Single Core 2 Core 3 Core 4 Core 5 Core
Black or Yellow/Green Blue and Brown or Yellow-Green, and Black Blue, Brown, Black, Grey, or Yellow/Green, Blue, Brown Blue, Brown, Black, Grey or Yellow/Green, Brown, Black, Grey Blue, Brown, Black, Grey, Black or Yellow/Green, Blue, Brown, Black, Grey

Technical DataTable

JAINSON 1.1 kV 3 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES (IS : 1554 PART 1)
CABLE CODE : YWY/YFY
SIZE (MM2) INSULATION PVC THICKNESS IN MM (NOM.) INNER SHEATH PVC THICKNESS IN MM (MIN.) ARMOUR SIZE IN MM (G.I) OUTER SHEATH PVC THICKNESS IN MM (MIN.) APPROX OUTER SHEATH O/D IN MM APPROX WEIGHT OF CABLE (KGS./KM) MAX.DC CONDUCTOR RESISTANCE at 20° C (Ohm/Km) Current Ratings (Amp.)
MAIN CORE HALF CORE W H Direct
In
Ground
In Air
3.5C X 25 0.90 0.70 0.30 4.0 0.80 1.40 22.70 1424 0.727 120 125
3.5C X 35 0.90 0.70 0.30 4.0 0.80 1.40 24.50 1748 0.524 145 155
3.5C X 50 1.00 0.90 0.30 4.0 0.80 1.56 28.50 2391 0.387 170 190
3.5C X 70 1.10 0.90 0.40 4.0 0.80 1.50 32.15 3108 0.268 210 235
3.5C X 95 1.10 1.00 0.40 4.0 0.80 1.56 36.10 4082 0.193 250 290
3.5C X 120 1.20 1.10 0.50 4.0 0.80 1.72 40.50 5135 0.153 285 330
3.5C X 150 1.40 1.10 0.50 4.0 0.80 1.88 44.10 6137 0.124 315 375
3.5C X 185 1.60 1.10 0.60 4.0 0.80 2.04 49.15 7542 0.0991 355 435
3.5C X 240 1.70 1.20 0.70 4.0 0.80 2.20 54.60 9433 0.0754 410 510
3.5C X 300 1.80 1.40 0.80 4.0 0.80 2.36 60.40 11567 0.0601 460 590
3.5C X 400 2.00 1.60 0.80 4.0 0.80 2.52 68.10 14983 0.0470 520 670
3.5C X 500 2.20 1.70 1.00 4.0 0.80 2.84 76.10 18699 0.0366 580 750

Technical DataTable

JAINSON 1.1 kV 3 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES (IS : 1554 PART 1)
CABLE CODE : YWY/YFY
SIZE (MM2) INSULATION PVC THICKNESS IN MM (NOM.) INNER SHEATH PVC THICKNESS IN MM (MIN.) ARMOUR SIZE IN MM (G.I) OUTER SHEATH PVC THICKNESS IN MM (MIN.) APPROX OUTER SHEATH O/D IN MM APPROX WEIGHT OF CABLE (KGS./KM) MAX.DC CONDUCTOR RESISTANCE at 20° C (Ohm/Km) Current Ratings (Amp.)
W H Direct
In
Ground
In Air
3 C X 1.5 0.80 0.30 1.40 1.24 13.20 377 12.10 21 17
3 C X 2.5 0.90 0.30 1.40 1.24 14.40 454 7.41 27 24
3 C X 4 1.00 0.30 1.40 1.24 16.50 603 4.61 36 30
3 C X 6 1.00 0.30 1.40 1.40 17.90 720 3.08 45 39
3 C X 10 1.00 0.30 4.0 0.80 1.40 18.85 828 1.83 60 52
3 C X 16 1.00 0.30 4.0 0.80 1.40 21.00 1092 1.15 77 66
3 C X 25 1.20 0.30 4.0 0.80 1.40 21.60 1270 0.727 99 90
3 C X 35 1.20 0.30 4.0 0.80 1.40 23.50 1602 0.524 120 110
3 C X 50 1.40 0.30 4.0 0.80 1.40 26.85 2141 0.387 145 135
3 C X 70 1.40 0.40 4.0 0.80 1.56 29.95 2762 0.268 175 165
3 C X 95 1.60 0.40 4.0 0.80 1.56 33.90 3636 0.193 210 200
3 C X 120 1.60 0.40 4.0 0.80 1.56 36.55 4438 0.153 240 230
3 C X 150 1.80 0.50 4.0 0.80 1.72 40.60 5448 0.124 270 265
3 C X 185 2.00 0.50 4.0 0.80 1.88 44.50 6555 0.0991 300 305
3 C X 240 2.20 0.60 4.0 0.80 2.04 49.60 8220 0.0754 345 355
3 C X 300 2.40 0.60 4.0 0.80 2.20 54.70 10112 0.0601 385 400
3 C X 400 2.60 0.70 4.0 0.80 2.36 61.60 13208 0.0470 425 455

Technical DataTable

JAINSON 1.1 kV 4 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES (IS : 1554 PART 1)
CABLE CODE : YWY/YFY
SIZE (MM2) INSULATION PVC THICKNESS IN MM (NOM.) INNER SHEATH PVC THICKNESS IN MM (MIN.) ARMOUR SIZE IN MM (G.I) OUTER SHEATH PVC THICKNESS IN MM (MIN.) APPROX OUTER SHEATH O/D IN MM APPROX WEIGHT OF CABLE (KGS./KM) MAX.DC CONDUCTOR RESISTANCE at 20° C (Ohm/Km) Current Ratings (Amp.)
W H Direct
In
Ground
In Air
4 C X 1.5 0.80 0.30 1.40 1.24 14.10 446 12.10 21 17
4 C X 2.5 0.90 0.30 1.40 1.24 15.40 544 7.41 27 24
4 C X 4 1.00 0.30 1.40 1.40 18.15 750 4.61 36 30
4 C X 6 1.00 0.30 1.40 1.40 18.20 778 3.08 45 39
4 C X 10 1.00 0.30 4.0 0.80 1.40 20.55 1041 1.83 60 52
4 C X 16 1.00 0.30 4.0 0.80 1.40 23.20 1398 1.15 77 66
4 C X 25 1.20 0.30 4.0 0.80 1.40 25.65 1690 0.727 99 90
4 C X 35 1.20 0.30 4.0 0.80 1.56 28.55 2168 0.524 120 110
4 C X 50 1.40 0.40 4.0 0.80 1.56 32.70 2904 0.387 145 135
4 C X 70 1.40 0.40 4.0 0.80 1.56 36.15 3698 0.268 175 165
4 C X 95 1.60 0.40 4.0 0.80 1.72 41.45 4913 0.193 210 200
4 C X 120 1.60 0.50 4.0 0.80 1.88 45.20 6030 0.153 240 230
4 C X 150 1.80 0.50 4.0 0.80 2.04 49.95 7370 0.124 270 265
4 C X 185 2.00 0.60 4.0 0.80 2.20 55.10 8916 0.0991 300 305
4 C X 240 2.20 0.60 4.0 0.80 2.36 61.20 11137 0.0754 345 355
4 C X 300 2.40 0.70 4.0 0.80 2.52 67.70 13715 0.0601 385 400
4 C X 400 2.60 0.70 4.0 0.80 2.84 76.75 17961 0.0470 425 455